XT7L M 1600 Ekip Touch LSIG In1600 3p FF - 1SDA101513R1

Power circuit-breaker for trafo/generator/installation protection Tmax XT XT7L M 1600 Ekip Touch LSIG In1600 3 pole fixed execution front terminals solid-state release

XT7L M 1600 Ekip Touch LSIG In1600 3p FF

1SDA101513R1

 

General information
Assortment  Netherlands
Order code 1SDA101513R1
Class name EC000228 - Power circuit-breaker for trafo/generator/installation protection
Brand ABB Componenten
Series Tmax XT
Type XT7L M 1600 Ekip Touch LSIG In1600 3p FF
Description XT7L M 1600 Ekip Touch LSIG In1600 3 pole fixed execution front terminals solid-state release
vermogensautomaat Tmax XT7L 1600, vast, driepolig, met frontaansluitklemmen en veerenergiemechanisme en hendelbedieningsmechanisme en electronische beveiliging in AC Ekip Touch LSIG R 1600
Status Not in stock - Active
Estimated delivery time 22 calendar days
GTIN code 8056221015578
Net weight 9.7 Kilogram
Country of origin DE
Country of production origin IT
Price
Gross price € 9887.00 per 1 PC
Price date 01-04-2026
Condition group DU
Logistic data
Product code describes 1 PC
Minimum order quantity 1 PC
Delivery unit 1 PC
Gross weight 9.7 Kilogram
Package dimensions (l x w x h) 360 x 280 x 350 Millimeter
Statistic code 85362090
Specifications
Rated permanent current Iu (ampere) 1600
Rated voltage (volt) 690 - 690
Overload release current setting (ampere) 640 - 1600
Adjustment range short-term delayed short-circuit release (ampere) 960 - 16000
Adjustment range undelayed short-circuit release (ampere) 2400 - 24000
Integrated earth fault protection No
Type of electrical connection of main circuit Bolt connection
Device construction Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting No
DIN rail (top hat rail) mounting optional No
Number of auxiliary contacts as normally closed contact 0
Number of auxiliary contacts as normally open contact 0
Number of auxiliary contacts as change-over contact 0
With switched-off indicator No
Number of poles 3
Degree of protection (IP) IP20
Position of connection for main current circuit Front side
Type of control element Toggle
Complete device with protection unit Yes
Motor drive integrated No
Motor drive optional Yes
With integrated under voltage release No
Power loss (watt) 94