Power circuit-breaker for trafo/generator/installation protection Tmax Tmax T7H 1600/R1600 3P fixed execution front terminals PR331/P-LSIG microprocessor-based rel. In = 1600A Im = 960 - 24000A
T7H 1600/1600 PR331/P-LSIG FF 3
1SDA063028R1
| General information | |
|---|---|
| Assortment | Netherlands |
| Order code | 1SDA063028R1 |
| Class name | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Brand | ABB Componenten |
| Series | Tmax |
| Type | T7H 1600/1600 PR331/P-LSIG FF 3 |
| Description |
Tmax T7H 1600/R1600 3P fixed execution front terminals PR331/P-LSIG microprocessor-based rel. In = 1600A Im = 960 - 24000A
Vermogensautomaat TMAX T7H 1600, vaste uitvoering, driepolig, met frontklemmen en hendelbediening en elektronische beveiliging AC PR331/P-LSIG R 1600 |
| Status | Not in stock - Phase-out |
| Estimated delivery time | 57 calendar days |
| Replacement / Alternative | 1SDA100901R1 |
| GTIN code | 8015644655778 |
| Net weight | 9.7 Kilogram |
| Country of origin | DE |
| Country of production origin | IT |
| Price | |
|---|---|
| Gross price | € 15063.00 per 1 PC |
| Price date | 01-04-2026 |
| Condition group | D5 |
| Logistic data | |
|---|---|
| Product code describes | 1 PC |
| Minimum order quantity | 1 PC |
| Delivery unit | 1 PC |
| Gross weight | 9.7 Kilogram |
| Package dimensions (l x w x h) | 360 x 280 x 350 Millimeter |
| Statistic code | 85362090 |
| Specifications | |
|---|---|
| Rated permanent current Iu (ampere) | 1600 |
| Rated voltage (volt) | 690 - 690 |
| Overload release current setting (ampere) | 640 - 1600 |
| Adjustment range short-term delayed short-circuit release (ampere) | 960 - 16000 |
| Adjustment range undelayed short-circuit release (ampere) | 2400 - 19200 |
| Integrated earth fault protection | No |
| Type of electrical connection of main circuit | Bolt connection |
| Device construction | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting | No |
| DIN rail (top hat rail) mounting optional | No |
| Number of auxiliary contacts as normally closed contact | 0 |
| Number of auxiliary contacts as normally open contact | 0 |
| Number of auxiliary contacts as change-over contact | 0 |
| With switched-off indicator | No |
| Number of poles | 3 |
| Degree of protection (IP) | IP20 |
| Position of connection for main current circuit | Front side |
| Type of control element | Toggle |
| Complete device with protection unit | Yes |
| Motor drive integrated | No |
| Motor drive optional | Yes |
| With integrated under voltage release | No |
| Power loss (watt) | 77 |
×